What’s in the Box
The C-600HV Pump is shipped with the following contents:
- C-600HV Diaphragm Metering Pump
- Discharge injection fitting with check valve
- Suction/Discharge tube – clear PVC – 10′ length (5/8″ OD, 1/2″ ID)
- Suction foot strainer
- Hose Clamps
Preparation
The C-600HV Pump is designed to be installed indoors in a protected enclosure for maximum pump life. A cool, dry location where the unit can be easily monitored is recommended. Special ventilation is not required.
The pump can be mounted on a level surface or mount, where pump head is vertical with suction at the bottom and discharge at the top.
Piping and physical installation
The C-600HV Pump must be level with discharge facing up to ensure pumping accuracy. Choose a location that minimizes suction lift.
If mounting the pump to the wall or bracket, follow these instructions:
- Use the diagram and drawing on the manual (or below) to mount the bracket to a secure wall location. We recommend mounting the pump at a height where the display and indicator lights are easily visible, and where it can be easily serviced.
- Ensure the pump is mounted level and screws are secure and will support the weight of the pump and any connected tubing.
- Pump can also be mounted to customer-provided bracket and structure. Be sure pump is mounted so it can easily be adjusted (via cam) and serviced.
Connecting Suction and Discharge Tubing/Piping
The C-600HV Pump comes with ½” hose barb connections.
Before connecting the tubing to the pump, be sure the pump is OFF. Wear protective clothing and eye protection when connecting tubing to chemicals or chemical lines.
Connect the suction tubing to the pump, and place and secure the other end of suction tubing in the chemical tank/source. Using the provided foot valve/strainer is recommended.
Connect the discharge tubing to the pump and then connect the other end to the discharge point. If using the provided injection valve, be sure to mount it in an upward position to prevent air bubbles from collecting.
Wiring
Power Wiring
The C-600HV can be provided with motor powered by 100 to 240VAC, 50/60Hz power. There is no power cord provided. Pump must be field wired using customer-provided power cord or hard wired.
Be certain to connect the pump to the proper supply voltage. Using the incorrect voltage will damage the pump and may result in injury. The voltage requirement is printed on the pump serial label.
Note: When in doubt regarding your electrical installation, contact a licensed electrician
See the below Wiring Chart for information and specifications in connecting to your electrical and control system.
Motor Lead Wires
Input Voltage | Hot Lead wire | Neutral Lead wire | Ground Lead wire |
115V 60 Hz | Black or Yellow | Blue | Green |
220V 50 Hz | Blue or Yellow | Brown | Green |
230V 60 Hz | Black or Yellow | Red | Green |
240V 50 Hz | White or Yellow | Orange | Green |
24V 60 Hz | White | Blue | Green |
12 VDC | Black | White | N/A |
24 VDC | Black | White | N/A |
- Yellow lead wire = thermally protected motor, Black/Blue lead wired = standard impedance protected motor.
If you have a C-600 with Cyle Time Board (no longer offered), then see the below diagram for wiring instructions.